What size inverter does a camper van need? What 1000, 2000 and 3000 W can run

Pick the inverter from the appliances you run together, then check the part most guides skip: the battery, cable and fuse have to carry the current, and at 12 V that current is large.

By apprun.icuUpdated Read 9 minIncludes an inverter sizer
On this page
  1. The sizing rule
  2. What 1000, 2000 and 3000 W can actually run
  3. The battery side: current, cable and BMS
  4. Inverter sizer
  5. Do you need AC for the big loads?
  6. Questions people ask
  7. Put the plan to work
  8. Sources and method

The sizing rule

An inverter’s continuous rating is the load it can carry for hours. Running it at 100% leaves nothing for inverter losses, a sagging battery or a cold start, so the usual planning margin is 20 to 25%. Use the same rule the Van Power Calculator uses:

continuous rating ≥ peak simultaneous watts × 1.25
surge rating ≥ largest start-up watts × 1.5 Peak simultaneous watts means only the appliances that can be on at once. If you never run the kettle and the hob together, you do not add them.

Motors need a second check. A fridge compressor, blender, vacuum cleaner or air conditioner can draw two to three times its running watts for a moment as it starts, and an inverter that cannot supply that surge trips even though the running watts fit. Datasheets often list a surge rating around twice the continuous figure, so compare it with your largest start-up load.

Where the current goes in a 12 volt inverter system Power flows from the battery bank through a fuse and cable to the inverter and then to the AC appliances. At the inverter's full 2,000 watt rating the battery supplies about 185 amps at 12 volts, 93 amps at 24 volts or 46 amps at 48 volts. The cable is sized so the voltage drop stays within 3 percent, and the inverter turns about 10 percent of the power into heat. Battery bank12, 24 or 48 V up to 185 A at 12 V 93 A at 24 V · 46 A at 48 V Fuse and cablesized for the DC current 3% voltage-drop budget thicker cable, lower loss Inverterabout 90% efficient 2,000 W of AC the other 10% becomes heat AC appliances
Power flows top to bottom; the numbers are for a 2,000 W inverter at full load. The DC side carries the large current, so it is the part that needs thick cable, a proper fuse and a battery that can deliver it.

What 1000, 2000 and 3000 W can actually run

The table applies the 80% rule to typical appliance draws. “Yes” means the load is at or below 80% of the inverter’s continuous rating. “Tight” means it runs but leaves less than the recommended margin. “No” means it exceeds the rating. Draws are typical ranges; read the nameplate on your own appliance.

Which appliances each inverter can run, by continuous rating in watts (one appliance at a time)
Appliance6001000150020003000
Laptop chargertypical 65 WYesYesYesYesYes
Blendertypical 300–600 W · 400 W usedYesYesYesYesYes
Travel kettletypical 600–1,000 W · 750 W usedNoYesYesYesYes
Two-slice toastertypical 700–1,200 W · 800 W usedNoYesYesYesYes
Coffee machinetypical 600–1,200 W · 900 W usedNoTightYesYesYes
Microwave (800 W cooking)typical 1,100–1,500 W · 1,100 W usedNoNoYesYesYes
Induction hob, one zonetypical 1,200–2,000 W · 1,500 W usedNoNoTightYesYes
Kettle, 120 V typetypical about 1,500 WNoNoTightYesYes
Hair dryertypical 1,200–2,000 W · 1,500 W usedNoNoTightYesYes
Kettle, 230 V typetypical 2,000–3,000 W · 2,200 W usedNoNoNoNoYes

The kettle question. Kettles are the appliance most people ask about, and they split by mains voltage. A small travel kettle (about 600 to 1,000 W) runs on a 1000 W inverter. A 120 V-style kettle (about 1,500 W) needs 2000 W. A 230 V-style kettle (2,000 to 3,000 W) needs a 3000 W inverter.

A kettle is power-hungry but energy-light. Heating one litre of water from 20 °C to boiling takes about 93 Wh of heat (4.186 J per gram per kelvin, 80 K, 1,000 g). Allow roughly 100 to 115 Wh from the battery once kettle and inverter losses are counted. Two boils a day costs a small fraction of a daily energy budget, but needs an inverter and cable that can deliver 1,500 W or more for a few minutes.

The battery side: current, cable and BMS

An inverter draws DC current equal to its AC power divided by the battery voltage and the inverter’s efficiency: I = P ÷ (η × V). The table shows that current at each inverter’s full rating, assuming 90% efficiency.

Battery current at full inverter load (90% efficient)
Inverter12 V system24 V system48 V system
600 W56 A28 A14 A
1000 W93 A46 A23 A
1500 W139 A69 A35 A
2000 W185 A93 A46 A
3000 W278 A139 A69 A

Three things have to be able to carry that current:

  • The battery and its BMS. A lithium battery’s battery management system limits continuous discharge. A common 12.8 V, 100 A BMS can deliver at most about 1,280 W of DC power, which is roughly 1,150 W of AC after inverter losses, so it cannot run a 2000 W inverter at full load. Check the battery’s continuous discharge rating, parallel more batteries, or raise the system voltage.
  • The cable. Voltage lost in the cable is power wasted and a smaller supply at the inverter. The Van Power Calculator sizes copper for a 3% drop with A = 2 × L × I × 0.0178 ÷ (V × 0.03), where L is the one-way run in metres and 0.0178 Ω·mm²/m is the resistivity of copper.
  • The fuse. It sits on the positive cable as close to the battery as practical and must protect the cable, not just the inverter. Follow the inverter manufacturer’s fuse and cable table.

Voltage matters more than it looks. For the same power, doubling the system voltage halves the current and, at the same percentage drop, cuts the copper area to a quarter.

Copper needed for a 2,000 W inverter at 12, 24 and 48 voltsHorizontal bars of the minimum copper cross-section for a 2,000 W inverter with a 1.5 metre one-way cable run and a 3 percent voltage drop: 27.5 square millimetres at 12 volts, 6.9 at 24 volts and 1.7 at 48 volts.12 V27.5 mm²24 V6.9 mm²48 V1.7 mm²Minimum copper area (mm²)
Minimum copper for a 2,000 W inverter on a 1.5 m one-way run at a 3% drop. Rounded up to standard sizes that is 35 mm² at 12 V, 10 mm² at 24 V and 2.5 mm² at 48 V.
!

Planning aid, not an installation guide. The figures here size the equipment; they do not replace the inverter maker’s instructions or local electrical rules. Cable must also be rated for the current it carries, and hard-wired AC circuits and battery fusing are worth having checked by a qualified auto or marine electrician.

Inverter sizer

Tick the AC appliances that could be on at the same time and adjust the watts to your own nameplates. The page address updates with your choices, so you can copy it and share the exact result.

Camper van inverter sizer

Runs in your browser

AC appliances that run together

Your system

%
m
2,000 W
inverter, continuous rating
1,565 W
of AC load running together
185 A
battery current at the inverter’s full rating
35 mm²
cable for the run, 3% drop (about 2 AWG)
Size the whole system

Method: load = sum of ticked appliances; recommended = load × 1.25, rounded up to a common inverter size; current = rating ÷ (efficiency × voltage); cable area = 2 × run × current × 0.0178 ÷ (voltage × 0.03), rounded up to a standard size.

Do you need AC for the big loads?

The cheapest way to shrink an inverter is to take the heaviest loads off it. Heating loads, such as kettle, hob, toaster and heater, are the ones that force a 2000 W inverter.

  • Cook and boil with gas or diesel. A gas hob or a diesel heater with a hot-water option moves the largest loads off the battery altogether.
  • Use a low-wattage kettle. A travel kettle or a 12 V kettle boils more slowly but lets a smaller inverter and thinner cable do the job.
  • Keep the fridge on DC. A 12 V compressor fridge runs without the inverter and avoids its idle drain.
  • Run the big AC load only on shore power or when driving. If the hob or microwave only runs on a campsite hook-up, it need not set your inverter size.

Whatever you choose, switch the inverter off when you are not using AC: even with nothing plugged in it draws idle power from the battery.

Questions people ask

Can a 1000 W inverter run a kettle?

Only a small travel kettle of roughly 750 W or less, which fits within 80% of the rating. A standard 120 V-style kettle (about 1,500 W) needs a 2000 W inverter, and a 230 V-style kettle (2,000 to 3,000 W) needs 3000 W.

What size inverter do I need for a microwave?

A microwave sold as 800 W of cooking power typically draws about 1,100 to 1,500 W from the supply. By the 80% rule that needs a 1500 W inverter at minimum, and 2000 W is more comfortable.

Can I run an induction hob in a camper van?

Yes, with a 2000 W or larger inverter and a battery, cable and fuse that can deliver the current: about 185 A at 12 V for a 2000 W inverter at full load. A 24 V system halves that current. Single-zone induction hobs draw roughly 1,200 to 2,000 W while heating.

How many amps does a 2000 W inverter draw from a 12 V battery?

About 185 A at full load, from 2,000 ÷ (12 × 0.9). At 24 V it is about 93 A and at 48 V about 46 A. Real battery voltage sags under load, which raises the current slightly.

How big a battery do I need for a 2000 W inverter?

Two separate questions: power and energy. For power, the battery and its BMS must supply the current, about 185 A at 12 V at full load. For energy, divide the energy you use by inverter efficiency: running 1,500 W for 10 minutes uses 250 Wh of AC energy, or about 278 Wh from the battery at 90% efficiency.

Do I need a pure sine wave inverter?

It is the safe default for laptops, chargers, motors and anything with an electronic power supply. Modified sine wave units can be adequate for simple heating loads but can cause noise or problems with some electronics and motors.

Does an inverter use power when nothing is plugged in?

Yes. Inverters draw idle, or no-load, power just by being switched on. The figure varies by model, so check the datasheet and switch the inverter off when you do not need AC.

Should a camper van use 12 V, 24 V or 48 V?

For small loads 12 V is simple and has the widest choice of equipment. As inverter size rises past about 1,500 to 2,000 W, current and cable size become the main cost, and a higher voltage cuts both: doubling the voltage halves the current and quarters the copper at the same percentage voltage drop.

Put the plan to work

When comparing estimates or adding headroom, check which value is the baseline in our percentage change and difference guide. Use the Percentage Calculator to keep the arithmetic visible, and explore related planning workflows before choosing equipment.

Sources and method

  1. The sizing rules (continuous rating = peak AC load × 1.25, surge = largest start-up × 1.5) and the 3% voltage-drop cable formula are those documented in the Van Power Calculator, which also applies the copper resistivity of 0.0178 Ω·mm²/m.
  2. Heating water: energy = mass × specific heat × temperature rise, using 4.186 J per gram per kelvin for water.
  3. Typical appliance wattages are ranges, not measurements of your equipment; use the rating on each appliance’s nameplate.